DCE academy · Standards

EN 50600

The European series of standards for data centers, clearly explained

In Europe, one common series of standards answers how resilient a data center must be, how it is protected, and how its energy consumption is measured.

This page explains what EN 50600 is about and leads to its individual parts.

See the parts of the series

Introduction

What is EN 50600?

A common basis for the design, construction, and operation of data centers.

It was developed by experts from the member countries of the European standards organization CENELEC. Internationally, ISO and IEC continue the series as ISO/IEC 22237.

EN 50600 is the first European series of standards for data centers. It describes how a data center is designed, operated, and measured: from the building through power supply, cooling, and cabling to security and the energy indicators.

It applies to every data center, regardless of size and purpose, from a server room to a site with several buildings.

What the standard specifies

  • Which properties the infrastructure must have: which failures it withstands, how spaces are protected, where measurements are taken.
  • Which classes a data center is classified and designed by.

What it leaves open

  • Which technology and which products achieve these properties. The standard describes the result, not the solution.
  • The selection of IT equipment and software. Nor does it replace design work or a specification of services; it is their basis.

Benefits

What is it needed for?

  • A common language

    Owners, planners, installers, and auditors refer to the same terms and classes.

    Anyone who specifies an according to EN 50600 in a tender describes what the infrastructure must achieve without prescribing a particular technology.

  • Resilience as a reasoned decision

    How resilient a data center must be follows from an assessment of the business risk, not from habit.

    This protects against a design that does not cover the risk and against that nobody needs.

  • Proof for customers and auditors

    An operator can demonstrate which classes its data center achieves. In practice, anyone renting space in a data center asks exactly that.

  • Indicators that legislation refers to

    Parts 4‑x specify how indicators such as are calculated. The European reporting obligation for data centers and the German Energy Efficiency Act (EnEfG) draw on these methods.

Stakeholders

Who is it for?

The standard is aimed at everyone who plans, builds, operates, or audits a data center:

  • Owners and operators choose the classes based on the business risk and demonstrate them to customers.

  • Planners and architects translate the classes into the design of the building, power supply, cooling, cabling, and security.

  • Installers and integrators build to specifications that refer to the standard.

  • Auditors and inspectors assess whether design and documentation match the selected classes.

  • Operations and maintenance staff keep the infrastructure running so that the class is maintained even during maintenance.

  • Management and procurement use the class to decide how much resilience the company pays for, and compare offers against the same benchmark.

The basic idea

Three classifications

Part 1 of the series classifies every data center according to three criteria. It starts with an assessment of the : what are the consequences of a failure, and how likely is it? The classes follow from the answer.

Part 1: General conceptsTerms in the glossary

At the start

Assessment of the business risk

What are the consequences of a failure, and how likely is it?

  1. Availability

    Four classes describe which faults and maintenance work the infrastructure must withstand without failure, from a single supply path to a fault-tolerant design.

    The class is chosen per discipline; the data center only reaches a class when power supply, cooling, and cabling all meet it.

  2. Protection

    Each space is assigned a against unauthorized access, intrusion, and events such as fire or water.

    A data center therefore has no single Protection Class, but one per space and hazard.

  3. Energy efficiency enablement

    Three specify how finely energy consumption can be measured, from the entire data center down to the individual system.

    The owner chooses the level before design begins; the measurement points follow from it.

Frequently asked questions

Basic questions

No. EN 50600 is a standard, not a law; applying it is voluntary. It becomes binding when a contract, a tender, or an audit catalog makes it the basis, and in design and construction it counts as a recognized rule of engineering practice for data centers. What the law does require are indicators based on its methods: Delegated Regulation (EU) 2024/1364 obliges operators with 500 kW or more of IT power to report annually to a European database. In Germany, the German Energy Efficiency Act (EnEfG) requires operators with a non-redundant nominal connected load of 300 kW or more to provide annual information, and it names parts of the 4‑x series as the basis for the calculation.

Both describe resilience in four levels but follow different approaches. The Tier system is the classification of the Uptime Institute, a private company that also issues certifications itself; EN 50600 is a public standard developed by consensus within the European standards organizations. The standard sets the Availability Class per discipline, derives it from the business risk analysis, and leaves the technical solution open. Availability Class 3 is therefore not automatically the same as Tier III.

Yes, as an assessment by an independent inspection body. Inspection organizations and experts use a catalog of criteria to check whether design and documentation match the selected classes; the basis is the conformance requirements of Part 1, including the business risk analysis. The standard does not specify who may carry out the assessment. DCE academy does not certify data centers: it trains professionals in EN 50600 and certifies people.

Above all, certainty for an investment that has an effect over the entire operating life. The class determines how much resilience is built, and a higher class means a higher investment. Tenders that specify classes instead of technology make offers comparable against the same benchmark. This protects against bad investments in both directions: too little protection for the business risk, or redundancy that nobody needs.

The parts of the series

The series in detail

Part 1 is the basis of the series.

Five groups build on it: the 2‑x series for the design of the disciplines, 3‑x for operation and management, 4‑x for , 5‑x for a maturity model for energy management and sustainability, and the 99‑x with recommended practices.

3‑xOperation: how it runs

Page to follow: Operation and management (DIN EN 50600‑3‑1)

5‑x · 99‑xMaturity and reports

Page to follow: Maturity model (DIN CLC/TS 50600‑5‑1)

No page of its own: Technical Reports (CLC/TR 50600‑99‑x)

All parts as a table
PartTitleCurrent edition (DIN)International equivalent
DIN EN 50600‑1General concepts2019‑08 (new European edition 2026, German edition to follow) · ISO/IEC 22237‑1:2021
DIN EN 50600‑2‑1Building construction2021‑09 · ISO/IEC 22237‑2:2024
DIN EN 50600‑2‑2Power supply and distribution2019‑08 · ISO/IEC 22237‑3:2021
DIN EN 50600‑2‑3Environmental control2019‑08 · ISO/IEC 22237‑4:2021
DIN EN 50600‑2‑4Telecommunications cabling infrastructure2023‑09 · ISO/IEC TS 22237‑5:2018, successor as an International Standard at final draft stage (2026)
DIN EN 50600‑2‑5Security systems2021‑09 · ISO/IEC 22237‑6:2024
DIN CLC/TS 50600‑2‑10no page of its ownEarthquake risk and impact analysis ()2021 · ISO/IEC TS 22237‑30:2022
DIN EN 50600‑3‑1Page to followManagement and operational information2016‑08 (new European edition 2026, German edition to follow; draft 2025‑09) · ISO/IEC TS 22237‑7:2018, successor in preparation
DIN EN 50600‑4‑1Overview of and general requirements for key performance indicators2017‑06 · ISO/IEC 30134‑1:2016 (basis, not identical)
DIN EN 50600‑4‑2Power Usage Effectiveness (PUE)2019‑08 · ISO/IEC 30134‑2:2026
DIN EN 50600‑4‑3Renewable Energy Factor (REF)2019‑08 · ISO/IEC 30134‑3
DIN EN 50600‑4‑6Energy Reuse Factor (ERF)2020‑07 · ISO/IEC 30134‑6
DIN EN 50600‑4‑7Cooling Efficiency Ratio (CER)2020‑11 · ISO/IEC 30134‑7
DIN EN 50600‑4‑8Carbon Usage Effectiveness (CUE)2023‑08 · ISO/IEC 30134‑8:2022
DIN EN 50600‑4‑9Water Usage Effectiveness (WUE)2023‑08 · ISO/IEC 30134‑9:2022
DIN CLC/TS 50600‑4‑31Key performance indicators for resilience (Technical Specification)2025‑02 · ISO/IEC TS 22237‑31 (basis: 2023 edition; second edition 2026)
DIN CLC/TS 50600‑5‑1Page to followMaturity model for energy management and environmental sustainability (Technical Specification)2023‑12 · no ISO counterpart
CLC/TR 50600‑99‑1no page of its ownRecommended practices for energy managementtransferred to CLC/TS 50600‑5‑1 · no ISO counterpart
CLC/TR 50600‑99‑2no page of its ownRecommended practices for environmental sustainabilitytransferred to CLC/TS 50600‑5‑1 · no ISO counterpart
CLC/TR 50600‑99‑3no page of its ownGuidance to the application of EN 50600 series2018 · no ISO counterpart
Editions over time
YearEuropean (EN, CLC/TS, CLC/TR)International (ISO/IEC)
2012European: EN 50600‑1, first editionInternational:
2014European: EN 50600‑2‑1, EN 50600‑2‑2, EN 50600‑2‑3, first editionsInternational:
2015European: EN 50600‑2‑4, first editionInternational:
2016European: EN 50600‑2‑5, EN 50600‑3‑1, EN 50600‑4‑1, 4‑2, 4‑3, first editionsInternational:
2018European: CLC/TR 50600‑99‑3International: ISO/IEC TS 22237‑1 to -7
2019European: EN 50600‑1, 2‑2, 2‑3 (second editions), 4‑2 and 4‑3 with amendment A1International:
2020European: EN 50600‑4‑6, EN 50600‑4‑7International:
2021European: EN 50600‑2‑1, EN 50600‑2‑5 (second editions), CLC/TS 50600‑2‑10International: ISO/IEC 22237‑1, -3, -4
2022European: CLC/TS 50600‑5‑1, first editionInternational: ISO/IEC TS 22237‑30
2023European: EN 50600‑2‑4 (second edition), EN 50600‑4‑8, EN 50600‑4‑9, CLC/TS 50600‑5‑1 (second edition)International:
2024European: International: ISO/IEC 22237‑2, -6; Delegated Regulation (EU) 2024/1364 links PUE, REF, ERF, WUE to EN 50600‑4‑x and ISO/IEC 30134
2025European: CLC/TS 50600‑4‑31; DIN EN 50600‑3‑1 as a draft (2025‑09)International:
2026European: New editions EN 50600‑3‑1 and EN 50600‑1 (August) published, German editions to follow; drafts prEN 50600‑2‑2 Ed. 3 (January 2026), prEN 50600‑2‑3International: ISO/IEC 30134‑2 (second edition, January), ISO/IEC TS 22237‑31 (second edition, February), ISO/IEC 22237‑5 at final draft stage (May)

Status of the standards

Current editions and ongoing revisions

All parts of the series apply in the edition listed in the table above. New European editions of Part 1 and Part 3‑1 have been published; their German editions are still pending. Parts 2‑2 and 2‑3 are available as drafts. Until the German edition appears, the previous DIN edition remains valid. Last reviewed on 8 October 2026.

EN 50600‑1
Current in Germany2019 edition
New edition or draft: New editionNew edition EN 50600‑1:2026 published at European level in August 2026; German edition pending.
EN 50600‑2‑2
Current in Germany2019 edition
New edition or draft: DraftEdition 3 in draft (prEN 50600‑2‑2:2026, January 2026); comments by the German mirror committee completed in March 2026.
EN 50600‑2‑3
Current in Germany2019 edition
New edition or draft: DraftDraft prEN 50600‑2‑3:2026.
EN 50600‑3‑1
Current in Germany2016 edition
New edition or draft: New editionNew edition EN 50600‑3‑1:2026 published at European level; German edition pending, draft DIN EN 50600‑3‑1:2025‑09.

A draft is not a standard and does not replace the current edition; the section “Who makes the standard” explains why.

Standardization

Who makes the standard

Three levels

International

ISO/IEC JTC 1/SC 39

ISO/IEC 22237

European

CENELEC CLC/TC 215

EN 50600

National

DKE/GK 719 “Rechenzentren”

DIN EN 50600‑x

Internationally, continues the content as ISO/IEC 22237.

ISO and IEC continue the content of EN 50600 as the international series ISO/IEC 22237.

The parts first appeared in 2018 as Technical Specifications; since 2021, they have been published step by step as International Standards (ISO/IEC 22237‑1:2021, Foreword).

Five of the seven core parts are now available as International Standards. The indicators of the 4‑x series have their counterpart in the ISO/IEC 30134 series.

At European level, CENELEC Technical Committee develops the series through its working group WG 3; DKE holds the secretariat.

At national level, the German mirror committee “Rechenzentren” (data centers) coordinates the German comments and adopts the parts as DIN EN 50600‑x (VDE 0801‑600‑x).

Five stages to a valid standard

Drafts

  1. CDCommittee Draftworking draft, commented on by the mirror committees
  2. prENEnquiry draftsent to all CENELEC members with a comment period
  3. FprENFinal draftformal vote

Published edition: binding

  1. ENEuropean Standardratified
  2. DIN ENNational standardadoption in Germany

A (CD) is a working draft on which the national mirror committees comment.

The enquiry draft goes to all CENELEC members with a comment period; after the comments have been incorporated, the final draft goes to the formal vote.

If the vote is positive, the text is as an EN and by every member country, in Germany as DIN EN (DIN EN 50600‑1:2019, European foreword).

A “2026 draft” is therefore an interim stage; the published edition remains binding.

Sponsor of the ISO/IEC 22237 working group

DCE academy

Standardization work at DCE academy

DCE academy trainers contribute to the national working groups in which the German position on EN 50600 is developed, including the power supply working group of DKE/GK 719. We therefore know what is on these pages from working on the texts, not only from reading them.

Further reading

Glossary

Four terms that recur on every part page: (four qualitative levels from single path to fault tolerant), (four levels of physical security per space and supply path), (how finely energy consumption is measured), and (an enquiry draft, not a valid standard).

All terms with definitions and references

  • DIN EN 50600‑1:2019‑08, Introduction, European foreword, Clauses 1, 4, 5.3, 6.1, 7.1 to 7.4, national annex NA.2, title page
  • DIN EN 50600‑2‑1:2021‑09, DIN EN 50600‑2‑2:2019‑08, DIN EN 50600‑2‑3:2019‑08, DIN EN 50600‑2‑4:2023‑09, DIN EN 50600‑2‑5:2021‑09, DIN EN 50600‑4‑1:2017‑06, DIN EN 50600‑4‑2:2019‑08, DIN EN 50600‑4‑3:2019‑08, DIN EN 50600‑4‑6:2020‑07, DIN EN 50600‑4‑7:2020‑11, DIN EN 50600‑4‑8:2023‑08, DIN EN 50600‑4‑9:2023‑08: European and national forewords, introductions
  • DIN CLC/TS 50600‑4‑31:2025‑02, Introduction, national and European foreword
  • ISO/IEC 22237‑1:2021, Foreword and Introduction
  • Commission Delegated Regulation (EU) 2024/1364 of 14 March 2024, Articles 1 and 3, Annex III
  • German Energy Efficiency Act (EnEfG) of 13 November 2023, § 3 No. 24, § 13, Annex 3 (gesetze-im-internet.de, retrieved 2 October 2026)
  • Standards catalogs (as of 17 September 2026): iTeh (prEN 50600‑1:2026, prEN 50600‑2‑3:2026, EN 50600‑3‑1:2026), DIN Media (DIN EN 50600‑3‑1:2025‑09 draft, DIN CLC/TS 50600‑5‑1:2023‑12, CLC/TR 50600‑99‑3:2018), ISO catalog (22237-5, 22237-7, TS 22237‑30, TS 22237‑31), IEC Webstore (ISO/IEC 30134‑2:2026), CEN-CENELEC announcement of 1 December 2023 (99‑1/99‑2)
  • DKE committee page GK 719 (retrieved 17 September 2026); CENELEC committee page CLC/TC 215 (retrieved 17 September 2026); CENELEC BOSS “Enquiry” and “Formal Vote” (retrieved 17 September 2026)
  • DCE academy seminar practice: Data Center Design & Implementation (held November 2025), Data Center – General Principles (held April 2026)

Last reviewed on 17 September 2026 · DCE academy

Contact

Questions about applying EN 50600?

Thomas Wawra answers your questions about applying EN 50600 in your project, and which seminar suits it, by phone or email.

Newsletter

Expert articles and standards updates by email

Expert articles from the newsroom, news from standardization, and the next seminar dates.

DCE academy GmbH newsletter: expert articles, standardization news and seminar offers by email, about once a month, plus occasional notices about individual seminars. The newsletter is published in German. We count anonymously how often an issue is opened; this is never linked to you. You can unsubscribe at any time, which withdraws your consent, via the link in every email or at info@dce-academy.com. Details in our privacy policy.