Skip to content

EN 50600‑1VDE 0801‑600‑1

General concepts

EN 50600‑1 is the part that every other part of the series builds on. It defines how a data center is structured from the perspective of the standard, how risks are assessed, and by which three criteria its infrastructures are classified: availability, physical security, and .

Current edition 2019‑08 · New European edition 2026, German edition to follow

What it is about

Part 1 provides the terms, the reference models, and the classification system to which all design parts of the series refer. Every standard on the building, power supply, cooling, cabling, or security asks first: which classes has the owner selected?

The standard applies to all data centers regardless of size and type of construction, from the server room to the colocation site, and is aimed at owners, operators, designers, installers, auditors, and maintenance providers. It does not cover the selection of IT equipment and software, availability analysis across multiple sites, or safety and EMC requirements (EN 50600‑1:2019, Introduction and Clause 1).

Core requirements in our own words

  1. Conformance starts with the risk analysis.

    A design conforms to Part 1 only if a exists and the , , and are derived from it. Clauses 4 and 5.1.

  2. Risk is impact times probability.

    Both are assessed in four levels and shown in a matrix; external threats to the location and the cost per outage are part of this. The standard does not prescribe a method. Clause 5.3.

  3. Four Availability Classes, selected per discipline.

    Power supply, cooling, and cabling are each classified individually in Class 1 to 4, from single path to fault tolerant. The data center reaches a class only when every discipline meets it. Clause 7.2.2.

  4. No percentage values.

    The standard describes structure and redundancy, not availability in nines after the decimal point, because a power outage of one second has different consequences than minutes without cooling. Clause 5.1 and Annex A.

  5. Protection Classes per space and supply path.

    Each space is assigned a Protection Class against unauthorized access, intrusion, and internal and external environmental events. The specific requirements are set out in Parts 2‑1 to 2‑5. Clause 7.3.

  6. Measurability is defined before design.

    The owner selects one of three granularity levels, from the data center as a whole down to the individual system. The measurement points of the design parts follow from this. Clause 7.4.1.

From our seminars: two misconceptions

“Availability Class 3 is the same as Tier III.”

Both systems say similar things about redundancy. The standard, however, describes results and leaves the technical solution open; the criteria catalogs of individual certifiers work with individual criteria. Proof of conformance with EN 50600 needs the risk analysis as its justification, not just the list of components.

“You can skip the risk analysis if you build Class 3 straight away.”

In projects, we often see the class being fixed before anyone has assessed the business risk. The standard makes the analysis a condition of conformance: the class, the redundancy per discipline, the Protection Classes, and the metering concept all follow from it.

Where Part 1 applies in a project

  • Strategy phase

    Owner and designer assess the business risk and derive the classes and the metering concept. These decisions determine the investment for the entire service life.

  • Tendering

    The specification states the classes and describes in functional terms what the infrastructure must achieve, instead of prescribing a technology.

  • Audit and leasing

    The operator demonstrates to customers, insurers, or auditors which class the data center actually achieves.

This protects you from a class that does not cover the business risk or that finances redundancy nobody needs. The design process of the standard provides for this assessment before detailed design (Clause 8).

Status and revision

Current edition

DIN EN 50600‑1:2019‑08, German edition of EN 50600‑1:2019; supersedes the 2012 edition.

International

ISO/IEC 22237‑1:2021.

Revision

New edition EN 50600‑1:2026, published at European level since August 2026; the German edition is pending. Until then, the 2019 edition applies in Germany. Committee , German mirror committee DKE/GK 719.

Last reviewed

EN 50600‑1

Frequently asked questions

No, it is a European Standard, not a legal regulation. It becomes binding through contracts, specifications, and criteria catalogs, and it is regarded as a generally recognized rule of technology for data centers.

A qualitative classification of the infrastructure in four classes, from single path to fault tolerant. It describes which faults and which maintenance the power supply, cooling, and cabling must withstand without shutting down the load (Clause 7.2).

Yes, without it conformance with Part 1 is not possible. The Availability Class, Protection Classes, and granularity level are derived from it (Clauses 4 and 5).

Yes, to all data centers regardless of size and type of construction. A small server room may combine functions in one room but must be classified in the same way (Clause 6.2).

Yes. The new European edition EN 50600‑1:2026 was published in August 2026; the German edition is still pending. Until it appears, DIN EN 50600‑1:2019‑08 applies in Germany.

  • DIN EN 50600‑1:2019‑08 (German edition of EN 50600‑1:2019), Introduction, Clauses 1, 4, 5.1, 5.3, 6.2, 7.1 to 7.4, 8.1, Annex A, NA.2 (national annex of the German edition)
  • ISO/IEC 22237‑1:2021
  • EN 50600‑1:2026 (CLC/TC 215), BSI and iTeh catalog entries; DIN EN 50600‑1:2019‑08 listed as current by VDE Verlag; retrieved 8 October 2026
  • DCE academy seminar practice: Data Center – General Principles (session April 2026), Data Center Design & Implementation (session November 2025)

Contact

Questions about applying EN 50600?

Thomas Wawra answers your questions about applying EN 50600 in your project, and which seminar suits it, by phone or email.

Newsletter

Expert articles and standards updates by email

Expert articles from the newsroom, news from standardization, and the next seminar dates.

DCE academy GmbH newsletter: expert articles, standardization news and seminar offers by email, about once a month, plus occasional notices about individual seminars. The newsletter is published in German. We count anonymously how often an issue is opened; this is never linked to you. You can unsubscribe at any time, which withdraws your consent, via the link in every email or at info@dce-academy.com. Details in our privacy policy.